BIN-IN
Activating the binary input
Safety position B.IN SPOS
Moving to a safety position.
Activated menu item
SAFEPOS
The actuator moves to the position set under
SAFEPOS.
Deactivated menu item
SAFEPOS
The actuator moves to the end position which it would assume in the zero-voltage state.
Switching over the operating mode B.IN M / A
Switching over the operating mode into MANUAL or AUTOMATIC.
Binary input = 0
Operating mode AUTOMATIC
Binary input = 1
Operating mode MANUAL
If the operating mode switchover has been selected, you can then no longer switch over the operating
mode using the MANUAL/AUTOMATIC key.
Type of binary input
normally closed
(0 ... 5 V = 1; 10 ... 30 V = 0)
normally open
(0 ... 5 V = 0; 10 ... 30 V = 1)
BIN-IN
Select the function of
the binary input
Type of binary input
B.IN SPOS
NORM OPN
Safety
position
NORM CLS
NORM OPN
NORM CLS
B.IN M / A
Operating mode
changeover