44 - 8630
I
NSTALLATION
* Electrical connection - multipole connectors
Marking of the multipole plugs or sockets and the contacts
M16
M8
M12
M8
Output signals to
SPC
Process value
Initiators (inductive proximity switches)
Operating voltage
ATTENTION!
Use of the 4 - 20 mA setpoint input
If the voltage supply of a TOP Control device fails in a row of such devices connected in
series, the input of the failed device will become high-impedance. This will cause the 4 -
20 mA standard signal to fail. If this occurs, please contact Bürkert Service directly.
With Profibus DP or DeviceNet:
The markings of the multipole plugs and sockets, and the contacts are to be found in the
respective chapters.
NOTE
TE
For connection to the technical earth (ground) (TE), a threaded stud with nut is
provided
on the connection module. To assure electromagnetic compatibility (EMC),
connect this stud to a suitable earthing (grounding) point using as short a cable as
possible (max. 30 cm).