Electrical connection - multipole connectors – Burkert Type 8630 User Manual

Page 46

Advertising
background image

44 - 8630

I

NSTALLATION

* Electrical connection - multipole connectors

Marking of the multipole plugs or sockets and the contacts

M16

M8

M12

M8

Output signals to
SPC

Process value

Initiators (inductive proximity switches)

Operating voltage

ATTENTION!

Use of the 4 - 20 mA setpoint input

If the voltage supply of a TOP Control device fails in a row of such devices connected in
series, the input of the failed device will become high-impedance. This will cause the 4 -
20 mA standard signal to fail. If this occurs, please contact Bürkert Service directly.
With Profibus DP or DeviceNet:
The markings of the multipole plugs and sockets, and the contacts are to be found in the
respective chapters.

NOTE

TE

For connection to the technical earth (ground) (TE), a threaded stud with nut is
provided

on the connection module. To assure electromagnetic compatibility (EMC),

connect this stud to a suitable earthing (grounding) point using as short a cable as
possible (max. 30 cm).