Error messages and malfunctions maintenance, Error messages on the lc display – Burkert Type 8630 User Manual

Page 156

Advertising
background image

154 - 8630

M

AINTENANCE

AND

ERROR

CORRECTION

ON

THE

PROCESS

CONTROLLER

Error messages on the LC display

When operated according to these Operating Instructions, the TOP Control Continuous is
maintenance free.

Error messages and malfunctions

Maintenance

Error messages on execution of the function

X.TUNE

General error messages

Display

Causes of error

Remedy

X.ERR 1

No compressed air connected

Connect compressed air

X.ERR 2

Compressed air failure during

AUTOTUNE

Check compressed air supply

X.ERR 3

Actuator or positioning system leaky
on exhaust side

None, device faulty

X.ERR 4

Actuator system leaky on pressurized
side

None, device faulty

X.ERR 6

The end positions for POS-MIN and

POS-MAX are too near to each other

Check whether the allocation of the end
positions to POS-MIN and POS-MAX via
the function TUNE-POS is correct.

If incorrect:
Execution TUNE-POS again.
If correct:

TUNE-POS with this arrangement of the

end positions is not possible since they
are too close together.

X.ERR 7

False allocation of POS-MIN and POS-
MAX

To determine POS-MIN and POS-MAX,

move the actuator in each case in the

direction shown on the display.

Display

Causes of error

Remedy

CMD FAUL

signal error

check signal

set-value, positioner

SP FAULT

signal error

check signal

set-value, process controller

PV FAULT

signal error

check signal

actual value, process controller

PT FAULT

signal error

check signal

actual value, Pt-100

P1 FAULT

signal error

check signal

actual value, P1 fluid flow controller

P2 FAULT

signal error

check signal

actual value, P2 fluid flow controller

TMP FAUL

signal error

check signal

actual value, temperature, fluid flow controller

EE FAULT

EEPROM faulty

none, device faulty

MFI FAUL

Fieldbus board faulty