The proportional action factor Ks of the controlled member is obtained according from:

Ks =

Parameter setting according to Chien, Hrones and Reswick

∆ X

∆ Y

Controlle
type

P

PI

PID

Parameter setting

with aperiodic control event

with control event

(0 % overswing)

(with 20 % overswing)

Command

Kp = 0,3

Kp = 0,35

Tn = 1,2 Tg

Kp = 0,6

Tn = Tg
Tv = 0,5 · Tu

Disturbance

Kp = 0,3

Kp = 0,6

Tn = 4 · Tu

Kp = 0,95

Tn = 2,4 · Tu
Tv = 0,42 · Tu

Tg

Tu*Ks

Tg

Tu*Ks

Tg

Tu*Ks

Tg

Tu*Ks

Tg

Tu*Ks

Tg

Tu*Ks

Command

Kp = 0,7

Kp = 0,6

Tn = Tg

Kp = 0,95

Tn = 1,35 ·Tg
Tv = 0,47 · Tu

Disturbance

Kp = 0,7

Kp = 0,7

Tn = 2,3 · Tu

Kp = 1,2

Tn = 2 · Tu
Tv = 0,42 · Tu

Tg

Tu*Ks

Tg

Tu*Ks

Tg

Tu*Ks

Tg

Tu*Ks

Tg

Tu*Ks

Tg

Tu*Ks

Advertising