Terminal configuration with cable bushings – Burkert Type 8630 User Manual

Page 49

Advertising
background image

8630 - 47

I

NSTALLATION

* Electrical connection - terminals for cable bushing

➔ Remove the cover with the cable bushings to gain

access to the screw terminals. This is done by
unscrewing the 4 self-tapping screws.

Connection PCB of the TOP Control Continuous with screw
terminals and jumpers

Terminal

Allocation

External connection

1

Setpoint +

2

Setpoint GND

3

Analog position feedback +

4

Analog position feedback GND

5

Operating voltage +

6

Operating voltage GND

24 V DC ± 10 %
max. residual ripple 10 %

2

1

+ + (0/4 ... 20 mA or 0 ... 5/10 V

GND

5

6

Terminal configuration with cable bushings

GND

3

4

+ (0/4 ... 20 mA or 0 ... 5/10 V)

completely isolated electrically

ATTENTION!

Use of the 4 - 20 mA setpoint input

If the voltage supply of a TOP Control Continuous device fails in a row of such devices
connected in series, the input of the failed device will become high-impedance. This will
cause the 4 - 20 mA standard signal to fail. If this occurs, please contact Bürkert Service
directly.

NOTE

For connection to the technical earth (ground) (TE), a threaded stud with nut is
provided on the connection module. To assure electromagnetic compatibility
(EMC), connect this stud to a suitable earthing (grounding) point using as short a
cable as possible (max. 30 cm).