Burkert Type 8630 User Manual

Page 77

Advertising
background image

8630 - 75

O

PERATION

AND

C

ONTROLLER

F

UNCTIONS

SIG-ERR

Configuration of error recognition signal level

Configure error
recognition of
setpoint signal

Activate signal error
recognition

Configure error
recognition of
process value
signal

Move to safety
position if
signal in error

Move to safety
position if
signal error

When signal error recognition is activated, the error is displayed (see chapter:

Maintenance and Error

Correction).

NOTE

Error recognition
Error recognition can be selected only with 4 ... 20 mA, Pt100 and P1’P2 signals.
4 ... 20 mA
Error in input signal

≤ 3.5 mA (± 0.5 % of end value, hysteresis 0.5 % of end value)

Pt100
Error in input signal

≥ 225 °C (± 0.5 % of end value, hysteresis 0.5 % of end value)

P1’P2
Error in input signal

≤ 3.5 mA (± 0.5 % of end value, hysteresis 0.5 % of end value)

If other types of signal are selected or if the process controller is unactivated, the
respective branch of menu will be faded out. If because of this configuration neither of the
error recognition modes is possible, the message NOT.AVAIL is displayed in the selection
menu.

Safety position SPOS ON

If

SPOS ON is set, the following configurations may occur:

Activated menu item

SAFEPOS

On error recognition the actuatur moves to the position set under

SAFEPOS.

Deactivated menu item

SAFEPOS

On error recognition the actuator moves to the end position which it would assume in the zero-voltage
state.

INP OFF

SPOS OFF

ERR INP

INP ON

SPOS ON

ERR END

ERR P.INP

P.INP ON

SPOS ON

SIG-ERR

P.INP OFF

SPOS OFF

Activate move to safety