Burkert Type 8630 User Manual

Page 97

Advertising
background image

8630 - 95

O

PERATING

THE

PROCESS

CONTROLLER

P.CO - INP
Specification of the signal type for process actual value

Frequency signal (flow rate) 0 ... 1000 Hz

Connection with Pt100 (temperature)
- 20 °C ... + 220 °C

Configuration for flow rate controller - option

standard signal current 4 ... 20 mA (flow rate, pressure,
level)

Setting in 10 steps

P.CO - FILT
Filtering of the process actual value input

FILT XX
Setting in 10 steps: 0 ... 9

Valid for all types of process actual value.

Filter has low-pass behavior (PT1).

Range: 0 ... 9

Factory setting: 0

Setting

Corresponds to limiting

frequency (Hz)

Effect

0

10

minimum filtering

1

5

2

2

3

1

4

0.5

5

0.2

6

0.1

7

0.07

8

0.05

9

0.03

maximum filtering