Burkert Type 8630 User Manual
Page 97
Advertising

8630 - 95
O
PERATING
THE
PROCESS
CONTROLLER
P.CO - INP
Specification of the signal type for process actual value
Frequency signal (flow rate) 0 ... 1000 Hz
Connection with Pt100 (temperature)
- 20 °C ... + 220 °C
Configuration for flow rate controller - option
standard signal current 4 ... 20 mA (flow rate, pressure,
level)
Setting in 10 steps
P.CO - FILT
Filtering of the process actual value input
FILT XX
Setting in 10 steps: 0 ... 9
Valid for all types of process actual value.
Filter has low-pass behavior (PT1).
Range: 0 ... 9
Factory setting: 0
Setting
Corresponds to limiting
frequency (Hz)
Effect
0
10
minimum filtering
1
5
2
2
3
1
4
0.5
5
0.2
6
0.1
7
0.07
8
0.05
9
0.03
maximum filtering
Advertising