8630 - 93

O

PERATING

THE

PROCESS

CONTROLLER

Factory setting: 1%

(refers to the span of the process actual value scaled by means of SCAL

PV

and

PV )

This function assures that the process controller cuts in only above a certain control difference . The
function reduces wear on the solenoid valves in the TOP Control Continuous and the pneumatic
actuator.

Entering the dead band in %

Insensitivity range with process control

P.CO - DBND
Insensitivity range (dead band) of the process controller

Xd2

Xd2

Xd2'

Xd2'

to controller

Process
actual value
(PV)

Process setpoint
(SP)

Control
difference

Dead band