Burkert Type 8630 User Manual
Page 95
Advertising
![background image](/manuals/330003/95/background.png)
8630 - 93
O
PERATING
THE
PROCESS
CONTROLLER
Factory setting: 1%
(refers to the span of the process actual value scaled by means of SCAL
PV
and
PV )
This function assures that the process controller cuts in only above a certain control difference . The
function reduces wear on the solenoid valves in the TOP Control Continuous and the pneumatic
actuator.
Entering the dead band in %
Insensitivity range with process control
P.CO - DBND
Insensitivity range (dead band) of the process controller
Xd2
Xd2
Xd2'
Xd2'
to controller
Process
actual value
(PV)
Process setpoint
(SP)
Control
difference
Dead band