Commissioning and set-up as a positioner, Procedure for specifying the basic settings – Burkert Type 8630 User Manual

Page 55

Advertising
background image

8630 - 53

O

PERATION

AND

C

ONTROLLER

F

UNCTIONS

Configuration of the keys

MANUAL/AUTOMATIC-key

Switch between main and sub-menu items, e.g.
ACT FUNC - FUNCSNGL

Arrow keys

Switch between eual-ranking menu items, e.g.
ACTFUNC - INPUT

Commissioning and set-up as a positioner

➔ Before commissioning, execute the fluidic and electrical installations.

Procedure for specifying the basic settings

➔ On first commissioning of the TOP Control Continuous, carry out the following basic settings:

Specify the function of the pneumatic actuator used.

Specify the standard signal input for setpoint setting (4..20 mA, 0..20 mA, 0..10 V or 0..5 V).

Start the automatic adaptation of the positioner to the current operating conditions (AUTOTUNE).

Factory setting of the positioner

Function Factory setting

ACTFUNC FUNCSNGL

INPUT INP 4'20A

CHARACT CHA LIN

DIR.CMD DIR.CRISE

CUTOFF

CUT

= 0 %;

CUT

= 100 %

DIR.ACT DIR.ARISE

SPLTRNG

SR

= 0 (%);

SR = 100 (%)

X.LIMIT

LIM

= 0%,

LIM

= 100%

X.TIME

T.OPN Values determined by AUTOTUNE

T.CLS Values determined by AUTOTUNE

After execution of

SETFACT: 1 s

Function

Factory setting

OUTPUT

OUT ANL:
OUT POS

OUT 4'20 A

OUT BIN:
OUT DEV

DEV 5.0 NO

BIN-IN

B.IN SPOS

SPOS 000 NO

X.CONTROL

X.CO DBND

1 %

X.CO PARA
KX

Values determined by

AUTOTUNE

KX

Values determined by

AUTOTUNE

After execution of

SETFACT: 1

CODE

CODE 0000