Burkert Type 8630 User Manual
Page 34

32 - 8630
S
YSTEM
D
ESCRIPTION
Binary outputs
electrically isolated
current limitation
100 mA, output is clocked
Binary input
electrically isolated
0 ... 5 V = log "0", 10 ... 30 V = log "1"
inverted output reversed accordingly
PNEUMATIC DATA
Control medium
Qualitiy Classes to DIN ISO 8573-1
Dust content
Class 5
max. particle size 40 µm, max. particle density 10 mg/m
3
Water content
Class 3
max.pressure dew point
- 20 °C or min. 10 deg. below the lowest operating temperature
Oil content
Class 5
max. 25 mg/m³
Temperature range of
compressed air
-10 ... + 50 °C
Pressure range
3 ... 7 bar
Supply pressure variation
max. ± 10 % during operation
Air flow capacity of
control valve
100 l
N
/ min STP (for pressurizing and exhausting)
(Q
Nn
- value acc. to definition on pressure drop from 7 to 6 bar abs.)
Intrinsic air consumption
with zero control output
0.0 l
N
/min STP
Connections
G 1/4’’ internal thread G / NPT / RC