Settings in the menu items – Burkert Type 8630 User Manual

Page 40

Advertising
background image

38 - 8630

F

IRST

C

OMMISSIONING

After selection of the basic settings and return to the AUTOMATIC mode, the TOP

Control Continuous

works as a positioner.

Enter the position setpoint via the signal.

Switching between the
display options:

Display:

• Actual position of valve actuator

POS__XXX (0 ... 100 %)

• Setpoint position of valve actuator

CMD__XXX (0 ... 100 %)

• Input signal for setpoint position

INP__XXX

(here identical to setpoint position)

(0 ... 5/10 V or 0/4 ... 20 mA)

• Temperature inside

TOP Control Continuous housing

TEMP_XX.X (in °C)

Settings in the menu items

ACTFUNC

Actuator function

FUNC SNGL - single-acting

FUNC DOUB - double-acting

INPUT

Standard signal

INP 4’20A

- Current 4 ... 20 mA

INP 0’20A

- Current 0 ... 20 mA

INP 0’10V

- Voltage 0 ... 10 V

INP 0’5V

- Voltage 0 ... 5 V

ADDFUNCT

Jump over

X.TUNE

Initiate self-parametrization

END XX

Return to AUTOMATIC mode;

the display

EEPROM appears until the settings have been in the

memory.

Entering the position setpoint in the AUTOMATIC mode