Bus status display – Burkert Type 8630 User Manual

Page 129

Advertising
background image

8630 - 127

P

ROFIBUS

DP

PDO: Process Data Output

(from the control to TOP Control

Continuous)

Bus status display

Display message

Device status

Explanation/problem elimination

BUS OFFL

alternates with the
display value set

offline

Device is no connection to the bus

- bus connection incl. plug configuration correct?
- voltage supple and bus connection of the other

subscribers correct?

4 dots
to the left beneath the
display value set

online,
active
connection

Device is engaged in cyclic data exchange

The bus standard is indicated on the display.

Name

Description

Identifiers

PDO:INP

Set position (Input)
Set-value positioner in ‰, value range 0 ... 1000.

In the "pure" positioner operation (PCONTRL inanctive),

the transmission of the set position INP is required, as

process controller (PCONTRL active), the transmission of
INP is not possible.
If the value is too small or too large, the last valid value

will be used and will be displayed in ERR with HEX 14.

GSD file: PDO:INP

Identifiers (HEX): 81, 40, 14

PDO:SP

Process-set-value (Set-point)

Set-value process controller in physical unit (as set up in

the P.CO INP or P.CO SCAL menu), max. value range

-999 ... 9999, depending on the internal scaling.

If the value is too small or too large, the last valid value

will be used and will be displayed in ERR with HEX 15.

GSD file: PDO:SP

Identifiers (HEX): 81, 40, 15

PDO:MODE

Operation Mode
Value range 0 (AUTO) ... 1 (MANUAL) ...

12 (BUSSAFEPOS)

Operation mode:
0: AUTO 12: BUSSAFEPOS

1: HAND
If the value is too small or too large, the last valid value

will be used and will be displayed in ERR with HEX 16.

GSD file: PDO:MODE

Identifiers (HEX): 81, 00, 16

PDO:ERR

Reset of error message
If the value > 0, ERR is reset.

GSD file: PDO:ERR

Identifiers (HEX): 81, 00, 17

PDO:MTMP

Medium temperature

Temperature of the medium in °C. The value will be

predefined from the menu, the bus, or using a

temperature transmitter.
Value range -20 ... +150

If the value is too small or too large, the last valid value

will be used and will be displayed in ERR with HEX 18.

GSD file: PDO:MTMP

Identifiers (HEX): 81, 40, 18

PDO. INP is always active with the positioner, not present with process conroller.
PDO. SP can only be selected if the process controller is activated.
PDO. MTMP can only be selected if the fluid flow controller option is active.

NOTE