Burkert Type 8630 User Manual

Page 128

Advertising
background image

126 - 8630

P

ROFIBUS

DP

Finally, the process data output (from the controller to the TOP Control Continuous) is entered.

PDI

: Process Data Input (continued)

(from the TOP

Control Continuous to the controller)

PDI. PV and PDI. SP can only be selected if the process controller has been activated.
PDI.P1/P2/MTMP can only be selected if the fluid flow controller option is active.

NOTE

In the same order as in the selection in the TOP

Control Continuous and only process data

(

PDI) activated in the configuration menu may be entered.

The updating of the process data output only takes place in the MANUAL and
AUTOMATIC modes.

NOTE

Name

Description

Identifiers

PDI:P1

Forward pressure p1
Pressure in mbar (rel) that is present in front of the
process valve.

The value will be determined using a pressure
transmitter.
Value range -1013 ... +16000

GSD file: PDI:P1

Identifiers (HEX): 41, 40, 07

PDI:P2

Back pressure p2
Pressure in mbar (rel) that is present behind the
process valve.

The value will be determined using a pressure
transmitter.
Value range -1013 ... +16000

GSD file: PDI:P2

Identifiers (HEX): 41, 40, 08

PDI:MTMP

Medium temperature

Temperature of the medium in °C. The value will be

predefined from the menu, the bus, or using a

temperature transmitter.
Value range -20 ... +150

GSD file: PDI:MTMP

Identifiers (HEX): 41, 40, 09