Burkert Type 8630 User Manual

Page 110

Advertising
background image

108 - 8630

O

PERATING

THE

PROCESS

CONTROLLER

Step - Process tune ready to start

You are in the

process operating level in the AUTOMATIC mode (yellow LED in the MANUAL/

AUTOMATIC key flashes).

Make ready process tune by the following operating procedure:

The next setpoint step entered via the keypad (see Step ) is now used for parameter optimization. The
setpoint

SP is set equal to the actual sensor value PV and is the starting value for the optimization step.

Adaptation/modification of this starting value is described in Step .

Readiness of process tune is symbolized int he display by three horizontal bars behind the flashing
setpoint symbol

SP.

Step - Adaptation of the starting value for the optimization step (optional)

If required you can carry out an adaptation of the starting value for the optimization step. Switch the
device to the

MANUAL mode (LED in the MANUAL/AUTOMATIC key is off). By pressing the arrow keys,

open or close the process valve, which causes a corresponding change in the process value

PV. As

soon as the desired starting value is set, switch the device back to the

AUTOMATIC mode.

Step - Initiate process tune

You are in the

process operating level in the AUTOMATIC mode (yellow LED in the MANUAL/

AUTOMATIC key flashes).

Process tune is now initiated by entering via the keypad a setpoint step. This step should take place in
the future working range of the process control system.

The procedure is as follows:

Make ready

P.TUNE

(process tune)

process tune
ready

process tune
not ready

With the display

SP (setpoint) set, press one of the arrow keys for longer than 3

seconds to activate the mode for changing the process setpoint. After release of the
key, the first digit of the process setpoint flashes.

or

> 3 s

Set the value of the flashing digit of the process setpoint

SP.

Confirm the value set and move to the next digit. After confirmation of the fourth
digit, the process setpoint set is stored as the end value of the process setpoint
step.

or

Advertising