On operation of the TOP Control

Continuous as a process controller, the abovementioned position

control becomes a subordinate auxiliary control loop; the result is a cascade control. The process

controller in the main loop of the TOP Control Continuous has a PID function. The setpoint specified is

the process setpoint (SP) and it is compared with the process variable to be controlled. The actual

position (XPOS) of the pneumatic actuator is measured via the position sensing system. The controller

compares this actual value of the position with the setpoint (CMD) , which can be specified as a

standard signal. If a control difference (Xd1) exists, a pulse-width modulated voltage signal is sent to the

positioning system as the correcting variable. With single-acting actuators, if the difference is positive,

the pressurizing valve is driven via output B1. If it is negative, the exhaust valve is driven via output E1.

In this way, the position of the actuator is altered until the control difference is zero. Z2 represents a

disturbance.

* Operation as a process controller (option)

Process

Transmitter

Process
setpoint

Process controller

Valve
opening

CMD

PV

Xd2

SP

Z2

Process variable

Positioning
system Soleno-
id valves

Continuous
Valve

Position sensor

Positioner

Valve
opening

XPOS

Xd1

B1

E1

P

K

Z1

Process
control
loop

Example of process control:
TOP Control Continuous with sensor

Position control loop