Controller functions

Pulse length / pulse frequency controller

Pulse length controller (PLC)

The pulse length controller is used to operate a valve as an actuator.

It switches the contact on for a time that depends on the controller

output. The period is constant. A minimum ON time of 0.5 sec is

maintained even if the controller output takes corresponding values.

Pulse frequency controller (PFC)

The pulse frequency controller is used to operate a frequency-

controlled actuator. It varies the frequency with which the

contacts are switched on. The maximum pulse frequency

[pulses/min] can be defined. It depends on the actuator.

The contact ON time is constant. It is automatically calculated

from the user-defined maximum pulse frequency:

Output signal (relay contact) of pulse length controller

Output signal (relay contact) of pulse frequency controller

ON time (Y = 80 %)

ON time (Y = 20 %)

Pulse length

0

0

ON time

Pulse frequency (Y = 20%)

1
0

1
0

Pulse frequency (Y = 80%)