Tb sets the bar graph display, Sb sets the bar graph for a channel, Tn sets a scale – Yokogawa Value Series FX1000 User Manual

Page 102: Sv sets a measurement channel’s moving average, Sc sets a channel display color, Ta sets an alarm point mark

Advertising
background image

3-20

3.4 Setting Commands

IM 04L21B01-17EN

SE

Sets the line width and the

number of grid sections to use

on the trend graph

Syntax

SE p1,p2<terminator>
p1 Trend line width (1 to 3) in dots
p2 Number of grid segments (4 to 12, AUTO)

Query

SE?

Example Set the trend waveform line width to 1 dot and

the number of grid segments to 10.
SE1,10

TB

Sets the bar graph display

Syntax

TB p1<terminator>
p1 Bar graph display direction

HORIZONTAL
VERTICAL

Query

TB?

Example Display bar graphs horizontally.

TBHORIZONTAL

SB

Sets the bar graph for a channel

Syntax

SB p1,p2,p3<terminator>
p1 Measurement or computation channel

number

p2 Bar graph base position

NORMAL Normal (lower limit)
CENTER
LOWER Lower limit
UPPER Upper limit

p3 Number of scale divisions (4 to 12)

Query

SB[p1]?

Example Set the number of scale divisions on the bar

graph for channel 002 to 5, and display the bar
graph from the span lower limit (the scaling lower
limit if scaling is enabled).
SB002,NORMAL,5

Description You can specify computation channels (including

in queries) on models with the /M1, /PM1, or
/PWR1 math option.

TN

Sets a scale

Syntax

TN p1,p2,p3<terminator>
p1 Measurement or computation channel

number

p2 Display position (OFF, 1 to 6)
p3 Number of divisions (4 to 12, C10)

Query

TN[p1]?

Example Set the scale display position for channel 003 to

2, and set the number of divisions to 10.
TN003,2,10

Description You can specify computation channels (including

in queries) on models with the /M1, /PM1, or
/PWR1 math option.

SV

Sets a measurement channel’s

moving average

Syntax

SV p1,p2,p3<terminator>
p1 Measurement channel number
p2 Moving average (OFF, ON)
p3 Number of moving average samples (2 to

400)

Query

SV[p1]?

Example Set the number of moving average samples for

channel 002 to 12.
SV002,ON,12

SC

Sets a channel display color

Syntax

SC p1,p2<terminator>
p1 Measurement or computation channel

number

p2 Display color (see the SL command, which

is used to set a trip line)

Query

SC[p1]?

Example Set the channel 002 display color to blue.

SC002,BLUE

Description You can specify computation channels (including

in queries) on models with the /M1, /PM1, or
/PWR1 math option.

TA

Sets an alarm point mark

Syntax

TA p1,p2,p3,p4,p5,p6,p7<terminator>
p1 Measurement or computation channel

number

p2 Mark kind

ALARM Alarm mark
FIXED Fixed mark

p3 Scale board display (ON, OFF)
p4 Alarm level 1 display color (24 colors; see

the SL command, which is used to set a trip
line)

p5 Alarm level 2 display color (24 colors; see

the SL command, which is used to set a trip
line)

p6 Alarm level 3 display color (24 colors; see

the SL command, which is used to set a trip
line)

p7 Alarm level 4 display color (24 colors; see

the SL command, which is used to set a trip
line)

Query

TA[p1]?

Example Display alarm marks on the channel 004 scale.

TA004,ALARM,ON

Description You can specify computation channels (including

in queries) on models with the /M1, /PM1, or
/PWR1 math option.