Data dropout during modbus master – Yokogawa Value Series FX1000 User Manual

Page 192

Advertising
background image

App-2

IM 04L21B01-17EN

Data Dropout during Modbus Master

If the response to the previous command is not complete when the FX attempts to issue
a command to a slave device, the FX cannot issue the command causing a data dropout.
Take appropriate measures by referring to the following figures.

Read cycle

Data dropout

(slaves 2 and 3)

Data dropout

(slave 3)

Slave device 1

Slave device 2

Slave device 3

G

G

G

Read cycle

(Retry)

: Status lamp

: Response from the slave device

: Command from the FX

Data dropout

(slaves 2 and 3)

Data dropout

(slaves 2 and 3)

Disconnect slave 2

Slave device 1

Slave device 2

Slave device 3

Read cycle

Timeout value

Data dropout

(slaves 2 and 3)

Slave device 1

Slave device 2

Slave device 3

G

G

G

G

Y

Timeout value

G Y

Timeout value

R

1. When the response from the slave device takes a long time

2. When there is no response from the slave device

3. When the slave device that is not responding is disconnected (retry count is set to 1)

G

G

G

G

G

G

G

G

G

G

G

G

G

Y

R

Appendix 1 Data Dropout during Modbus Communication