1.8 Synchronizing the Time

The FX time can be synchronized to the time on an SNTP server. The FX can also
function as an SNTP server.

Setting the SNTP Client

Synchronize the FX time to the time on an SNTP server.
◊ Press

MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic

setting mode), and select the

Menu tab > Communication (Ethernet) > SNTP client.

• Use/Not

Select

Use to use the SNTP client function; Otherwise, select Not. If you select Use,

the SNTP client settings are displayed.

• SNTP server name

Set the SNTP server name using up to 64 alphanumeric characters.

• If the DNS is used, you can set the host name as a server name. For details on

setting the DNS, see section 1.3.

• You can also set the IP address. In this case, the DNS is not required.

• Port number

Enter the port number of the SNTP server in the range of 1 to 65535. The default

value is 123.

• Access interval

Set the time interval for synchronizing the time with the server to OFF, 1, 8, 12, or 24h.

If you select OFF, you can synchronize the time manually by operating soft keys. If the
difference between the FX time and the server time is greater than or equal to
10 minutes, the time is not corrected.

• Access reference time

Set the reference time for making queries.

• Access timeout

Set the time to wait for the response from the SNTP server when querying the time to

10, 30, 90s.

• Time adjust on Start action

Select

On to synchronize the time using SNTP when memory start is executed;

Otherwise, select

Off.

Manually Synchronizing the Time

You can synchronize the time at any time by operating the FUNC key. The SNTP client
setting must be enabled.
◊ Press

FUNC and select SNTP.

Advertising