Modbus Error Response (Common to Modbus server and Modbus slave)

The FX returns the following error codes to a client or master device.

Code

Error

Description

1

ILLEGAL FUNCTION

Invalid function code

An attempt was made to execute a function that is not

supported.

2

ILLEGAL DATA ADDRESS

Invalid register number

Failed to access the register.

3

ILLEGAL DATA VALUE

Invalid number of registers

When reading, the specified number of registers was less

than or equal to zero or greater than or equal to 126.
When writing, the specified number of registers was less

than or equal to zero or greater than or equal to 124.

7

NEGATIVE

ACKNOWLEDGE

Invalid contents written

• A lot number that is outside the valid range was

entered.

• Invalid characters (such as ‘¥x1b’) were written in

batch number or free message registers.

• Failed to control the following operations.

• Writing messages
• Writing free messages
• Writing batch numbers and lot numbers

However, no response is returned for the following errors.
• CRC error
• Errors other than those shown above

6.3 Modbus Protocol Specifications