App index configured alarm information data, Manual sampled data, Report data – Yokogawa Value Series FX1000 User Manual

Page 169

Advertising
background image

4-33

IM 04L21B01-17EN

Responses

1

2

3

4

5

6

App

Index

Configured Alarm Information Data

• The FE6 command is used to output the data.
• The ID number of the output format is 26.
• You can use the CB command to specify whether to output the data of measurement

channels set to skip and computation channels set to OFF.

• The figure below indicates the format.

Number of blocks

Block size

Configured alarm information block 1

• • •

Configured alarm information block n

(Reserved) (Reserved)

2 bytes

1 byte

1 byte

1 byte

1 byte

Version (Reserved)

2 bytes

Format Details

Item

Description

Output Value

Version

Format version

2

Number of blocks

1

Number of configured alarm information blocks

Up to 36

Block size

1

Size of the of configured alarm information blocks

32

Block 1 to n

Configured alarm information blocks

Up to 1152 bytes

See Block Details.

1: Output in the byte order specified by the BO command.

Block Details

Each value is the corresponding setting on the FX, but with the decimal point

removed. For example, “120” corresponds to a setting of “1.20” on the FX.

Item

Number

of Bytes Notes

Channel number

1

2

1 to 124

Decimal place

1

0 to 4

When you are using a channel that is set to Log scale,

2

the decimal place of the

FX digital display’s mantissa is displayed.

(Reserved)

1

0

Alarm type

4

The following settings are entered in order from level 1 to 4.
0: Setting off, 1: H (high limit), 2: L (low limit), 3: h (difference high limit),

4: l (difference low limit), 5: R (high limit on rate-of-change),

6: r (low limit on rate-of-change), 7: T (delay high limit), 8: t (delay low limit)

Alarm value

1

4x4

The alarm values are entered in order from level 1 to level 4.

When the Log scale

2

is not used: Alarm setting on the FX

When the Log scale

2

is used: The same value as the mantissa of the alarm setting

on the FX

Alarm value

(exponent)

1x4

The alarm values are entered in order from level 1 to level 4.
When the Log scale

2

is not used: 0

When the Log scale

2

is used: Same value as the exponent of the FX alarm setting

(Reserved)

4

0

1

Output in the byte order specified by the BO command.

2

/LG1 option

Manual Sampled Data

• The ME or MO command is used to output the data.
• The ID number of the output format is 17. See section 4.1.
• For the data format, see the FX1000 User’s Manual, IM 04L21B01-01EN.

Report Data

• The ME or MO command is used to output the data.
• The ID number of the output format is 18. See section 4.1.
• For the data format, see the FX1000 User’s Manual, IM 04L21B01-01EN.

4.3 Output Format of Binary Data