Input Register (shared with the Modbus slave function)

• Common Items

• The client device can only read the input registers.
• Decimal position and unit are not included. Specify them on the client device.

• Details

Input Register Data

Data Type

300001

Measured data of measurement channel 001

16-bit signed integer

|

|

300012 Measured data of measurement channel 012

• There is no decimal position information.

301001

Alarm status of measurement channel 001

Bit string

|

|

301012 Alarm status of measurement channel 012

• Register structure and alarm status values

2

1

4

3

4 bits

4 bits

4 bits

4 bits

4-bits

value Meaning

0

No alarm

1

High limit alarm

2

Low limit alarm

3

Difference high limit alarm

4

Difference low limit alarm

5

High limit on rate-of-change alarm

6

Low limit on rate-of-change alarm

7

Delay high limit alarm

8

Delay low limit alarm

Alarm level

Alarm status

302001

Lower bytes of the computed data of computation channel 101

32-bit signed integer

302002

Higher bytes of the computed data of computation channel 101

|

|

302047

Lower bytes of the computed data of computation channel 124

302048

Higher bytes of the computed data of computation channel 124

• Register structure

Example: Channel 101

Higher bytes

Lower bytes

Register 302002

Computed data

Register 302001

• There is no decimal position information.
303001

Alarm status of computation channel 101

Bit string

|

303024

Alarm status of computation channel 124

• The register structure and alarm status values are the same as the alarm status of

measurement channels.

6.3 Modbus Protocol Specifications