Rn sets basic login, Rp sets user limitations – Yokogawa Value Series FX1000 User Manual

Page 120

Advertising
background image

3-38

IM 04L21B01-17EN

RN

Sets basic login

Syntax

RN p1,p2<terminator>
p1 Auto logout (OFF, 1MIN, 2MIN, 5MIN,

10MIN)

p2 Operation without Login

OFF

Disables FX operation

DISPLAY Only enables screen operation

Query

RN?

Example Set the auto logout time to 1 minute, and disable

FX operation when logged out.
RN1MIN,OFF

RP

Sets user limitations

Syntax

RP p1,p2,...<terminator>
p1 User limitation number (1 to 10)
p2 User limitation item (KEY, FUNC, MEDIA)

Parameter p3 and subsequent parameters vary
as shown below depending on the p2 setting.

When p2 is set to KEY

Syntax

p3 START key (FREE, LOCK)
p4 STOP key (FREE, LOCK)
p5 MENU key (FREE, LOCK)
p6 USER key (FREE, LOCK)
p7 DISP/ENTER key (FREE, LOCK)

When p2 is set to FUNC (function key)

Syntax

p3 Alarm ACK (FREE, LOCK)
p4 Message and batch (FREE, LOCK)
p5 Computation (FREE, LOCK)
p6 Data save (FREE, LOCK)
p7 E-mail and FTP (FREE, LOCK)
p8 Time operations (FREE, LOCK)
p9 Display operations (FREE, LOCK)

Description Even on models that do not have the Ethernet

interface (/C7 option), if you set p2 to FUNC, you
can specify a value for parameter p7 (the E-mail
and FTP setting), but it will be ignored.

When p2 is set to MEDIA (external storage media)

Syntax

p3 External storage media operations (FREE,

LOCK)

p4 Setting load operations (FREE, LOCK)

Description You cannot use this command with p2 set to

MEDIA on models that do not have a CF card
slot or USB interface (/USB1 option).

Query

RP[p1,[p2]]?

Example Lock the START, STOP, and DISP/ENTER keys.

RP1,KEY,LOCK,LOCK,,,LOCK

RO

Sets the type of report and when

to create reports (/M1, /PM1, and

/PWR1 options)

When you are not creating reports

Syntax

RO p1<terminator>
p1 Report type (OFF)

Query

RO?

Example Set the FX to not create reports.

ROOFF

When you are creating hourly, daily, hourly + daily,

and daily + monthly reports

Syntax

RO p1,p2,p3<terminator>
p1 Report type

HOUR

Hourly report

DAY

Daily report

HOUR+DAY Hourly and daily reports
DAY+MONTH Daily and monthly reports

p2 Day to create reports (dd; fixed format)

dd

Day (01 to 28)

p3 Hour to create reports (hh; fixed format)

hh

Hour (00 to 23)

Query

RO?

Example Create daily reports at 09:00 every day (in

this case, parameter p2—which is 05 in this
example—is invalid).
RODAY,05,09

Description • You can use this command on models with the

/M1, /PM1, or /PWR1 math option.

• Parameter p2 is invalid if you specify it for

reports other than the monthly and daily
reports.

When you are creating daily + weekly reports

Syntax

RO p1,p2,p3<terminator>
p1 Report type (DAY+WEEK)
p2 Day of the week to create reports (SUN,

MON, TUE, WED, THU, FRI, SAT)

p3 Hour to create reports (hh; fixed format)

hh

Hour (00 to 23)

Query

RO?

Example Create daily reports at 09:00 every day and

weekly reports at 09:00 every Tuesday.
RODAY+WEEK,TUE,09

Description You can use this command on models with the

/M1, /PM1, or /PWR1 math option.

3.6 Basic Setting Commands

Advertising