3.4 Setting Commands

IM 04L21B01-17EN

3.4 Setting Commands

SR

Sets an input range

You cannot use this command to configure
settings while recording (memory sampling) or
computation is in progress.

When Setting Channels to Skip

Syntax

SR p1,p2<terminator>
p1 Measurement channel number
p2 Setting type (SKIP)

Query

SR[p1]?

Example Skip channel 001.

SR001,SKIP

Description • Channels set to SKIP are not measured.

• Set p1 by referring to the table in section 3.3.

When Setting the Channels to Voltage, TC, RTD, or

ON/OFF Input

Syntax

SR p1,p2,p3,p4,p5<terminator>
p1 Measurement channel number
p2 Input type

VOLT

DC voltage

TC

Thermocouple

RTD

Resistance temperature detector

DI

ON/OFF input

p3 Measuring range
p4 Span lower limit
p5 Span upper limit

Query

SR[p1]?

Example Set the channel 001 input type to TC type R, the

span lower limit to 0°C, and the span upper limit
to 1760.0°C.
SR001,TC,R,0,17600

Description • Set p1 and p3 by referring to the table in

section 3.3.

• For parameters p4 and p5, enter values with

five digits or less excluding the decimal point.

When Computing the Difference between Channels

Syntax

SR p1,p2,p3,p4,p5,p6,p7<terminator>
p1 Measurement channel number
p2 Setting type (DELTA)
p3 Input type

VOLT

DC voltage

TC

Thermocouple

RTD

Resistance temperature detector

DI

ON/OFF input

p4 Measuring range
p5 Span lower limit
p6 Span upper limit
p7 Reference channel number (measurement

channel number)

Query

SR[p1]?

Example Set the channel 010 setting type to differential

computation between channels with the
reference channel set to 001, and set the input
type to TC. Set the measuring range to R. Set the
span lower limit to 10.0°C and the span upper limit
to 100.0°C.
SR010,DELTA,TC,R,100,1000,001

Description • Set p1 and p4 by referring to the table in

section 3.3.

• For parameters p5 and p6, enter values with

five digits or less excluding the decimal point.

When Setting Channels to Scaling

Syntax

SR p1,p2,p3,p4,p5,p6,p7,p8,p9,p10
<terminator>
p1 Measurement channel number
p2 Setting type (SCALE)
p3 Input type

VOLT

DC voltage

TC

Thermocouple

RTD

Resistance temperature detector

DI

ON/OFF input

p4 Measuring range
p5 Span lower limit
p6 Span upper limit
p7 Scaling lower limit (–30000 to 30000)
p8 Scaling upper limit (–30000 to 30000)
p9 Scaling decimal place (0 to 4)
p10 Unit (up to 6 characters)

Query

SR[p1]?

Example Convert the DC voltage measured on channel

002 to DC current. Set the measuring range to
6 V, the span lower limit to 1 V, the span upper
limit to 5 V, the scaling lower limit to 1.00 A, and
the scaling upper limit to 5.00 A.
SR002,SCALE,VOLT,6V,1000,5000,100,
500,2,A

Description • Set p1 and p4 by referring to the table in

section 3.3.

• For parameters p5 and p6, enter values with

five digits or less excluding the decimal point.

• For parameters p7, p8, and p9, either set all

three parameters, or omit all three parameters.