Yokogawa Value Series FX1000 User Manual

Page 54

Advertising
background image

1-46

IM 04L21B01-17EN

Writing Measured Values to the Server

• Example

Write the measured value (16-bit signed integer) from channel 001 to register 40001

of instrument A.

16-bit signed integer

Measurement channel

Register of instrument A

001

40001

Command setting

W

001 - 001

1

40001

INT16

Writing Computed Values to the Server

• Example

Write the computed values (32-bit signed integers) from channel 101 to registers

40001 and 40002 of instrument A, in the order lower 16 bits/higher 16 bits. Only the
smallest register number need be specified in commands.

32-bit signed integer

Computation channel

Register of instrument A

40001
40002

101

lower bytes
higher bytes

Command setting

W-M

101 - 101

1

40001

INT32_L

1.10 Using Modbus to Read Data From and Write Data to Other Devices