1.9 Using the Modbus Server Function

The FX is used as a Modbus server.
For the Modbus specifications, see section 6.3.

Setting the Modbus Server

Carry out the steps below to enable another device to read the FX data or write data to
the FX using Modbus.
◊ Press

MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic

setting mode), and select the

Menu tab > Communication (Ethernet) > Server >

Server modes.

• Modbus

For the Modbus item under Server, select

Use or Not (don’t use).

◊ Press

MENU (to switch to setting mode), hold down FUNC for 3 s (to switch to basic

setting mode), and select the

Menu tab > Communication (Ethernet) > Server >

Allowed Modbus clients.

• Use/Not

To place a limitation on the IP addresses that can connect to the FX Modbus server,

select

Use. Only the IP addresses specified here can connect to the FX Modbus

server. To not place a limitation, select

Not.

• Client number

You can register up to 10 IP addresses. Select the client number from 1 to 10.

• On/Off

To allow connections, select

On.

• Allowed IP Address

Enter the IP address in the range of 0.0.0.0 to 255.255.255.255. You cannot enter a

host name.