5 using the modbus slave function, 5 using the modbus slave function -11 – Yokogawa Value Series FX1000 User Manual

Page 75

Advertising
background image

2-11

IM 04L21B01-17EN

Using the Serial Communication Interface (/C2 and /C3 Options)

1

2

3

4

5

6

App

Index

2.5 Using the Modbus Slave Function

The FX is used as a Modbus slave.
For the Modbus specifications, see section 6.3.

Setting the Serial Communication

Select

Modbus as a protocol on the Basic settings. For detail, see section 2.4, “Setting

the Serial Communication.”

Reading/Writing the FX Data on Another Device

Another device (master device) sends commands to the FX to read the FX data or write
data to the FX. You can perform some operations, such as memory start, by writing in the
registers.
For the function codes that the FX supports and the FX registers that the master device
can access, see “Modbus Server Function” in section 6.3.