Fm installation drawing – Weidmuller ACT20X User Manual

Page 107

Advertising
background image

Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)

1066540000/01/12.11

107

FM Installation Drawing


The module is available in the following variants:

Order No.

Installation Drawing

Type

8965400000

4 51478 Sheet 5-6

ACT20X-SDI-HDO-L-S

8965410000

4 51478 Sheet 5-6

ACT20X-SDI-HDO-H-S

8965420000

4 51478 Sheet 5-6

ACT20X-2SDI-2HDO-S

DANGER

For safe installation of ACT20X-(2)SDI-(2)HDO-(L/H)-S the following must be observed: The
module may only be installed by qualified personnel familiar with the national and international
laws, directives and standards that apply to this region.

DANGER

To prevent ignition of explosive atmospheres, disconnect power before servicing and do not

separate connectors when energized and an explosive gas mixture is present.

WARNING

Substitution of components may impair intrinsic safety and/or suitability for Division 2 / Zone 2.


The installation and wiring shall be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable ends.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The module must be installed in an enclosure suitable for the environment where it is used.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure according
to the regulations in the CEC for Canada or NEC for USA.
The module is galvanically isolated and does not require grounding.
Use 60/75 °C copper conductors in the wire size AWG 26-14.
The year of manufacture can be taken from the first two digits in the serial number.