Weidmuller ACT20X User Manual

Page 75

Advertising
background image

Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)

1066540000/01/12.11

75

Not connected

in hazardous area

-20 = Ta = 60 °C

or Zone 2

Non Hazardous area

Zone 0, 1, 2, 20, 21, 22

NAMUR Sensor

Contact Sensor

Switch w Shunt

Switch

Hazardous area

CBX200 for

Configuration

ACT20X

11

12

13

-

+

-

CH2

CH1

+

14

21

22

23

24

41

42

43

44

51

52

53

54

Configuration in

safe area only!

Illustration 7-22:

IECEx Installation Drawing

Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)

Ex Input

U

o

10.6 V DC

I

o

12 mA DC

P

o

32

mW

L

o

/R

o

1150

H/

Group

C

o

L

o

IIC 2

F 260

mH

IIB 6

F 780

mH

IIA 18

F 1000

mH

Terminal (41, 42, 43, 44) and (51, 52, 53, 54)

Supply / Output

U

m

253 V, max. 400 Hz