Weidmuller ACT20X User Manual
Page 126
Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)
126
1066540000/01/12.11
Terminal (24–22, 22–21)
Input
Group
C
o
L
o
L
o
/R
o
U
o
28 V
IIC
80 nF
4.2 mH
54 µH/Ω
I
o
93 mA
IIB
640 nF
16 mH
218 µH/Ω
P
o
0.65 W
IIA
2.1 µF
32 mH
436 µH/Ω
Terminal (41, 42, 43, 44) and (51, 52, 53, 54)
Supply / Output
U
m
253 V, max. 400 Hz
Terminal (51, 52)
Supply
Voltage
19.2…31.2 V DC
Terminal (43, 44)
Relay Output
Non Hazardous
Location
Zone 2 Installation
Voltage max.
250 V AC / 30 V DC
32 V AC / 30 V DC
Current max.
2 A AC / 2 A DC
2 A AC / 2 A DC
Power max.
500 VA / 60 W
64 VA / 60 W
Terminal (53, 54)
Status Relay
Non Hazardous
Location
Zone 2 Installation
Voltage max.
125 V AC / 110 V DC
32 V AC / 32 V DC
Current max.
0.5 A AC / 0.3 A DC
0.5 A AC / 1 A DC
Power max.
62.5 VA / 32 W
16 VA / 32 W