Weidmuller ACT20X User Manual

Page 65

Advertising
background image

Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)

1066540000/01/12.11

65

Ex Output signals

Input signals

Power Supply and Module Status

Zone 0, 1, 2, 20, 21, 22 /
Cl. I/II/III, div. 1 gr. A-G

Zone 2 / FM Cl. 1, div. 2,
gr. A-D or safe area

24

23

22

21

51

52

53

54

Module status

Module status

Gnd.

Supply +19.2...31.2 V DC

N.C.

14

12

11

13

42

41

44

43

Analogue, 4...20 mA

Load

4...20 mA

Load

4...20 mA

Channel 1:

Channel 1:

Channel 2:

Channel 2:

Illustration 7-20:

Applications

Current Input

Measurement range

3.5…23 mA

Input resistance

nom. 20 Ω + PTC 50 Ω

Alarm setpoint, low/high limit (programmable)

0…28 mA

Sensor error detection

< 1 mA

Current Output

Signal range (programmable)

3.5…23 mA

Load max.

20 mA / 725 Ω / 14.5 V DC

Load stability

≤ 0.01 % of span / 100 Ω