Weidmuller ACT20X User Manual

Page 67

Advertising
background image

Product Installation / Operation, ACT20X-SAI-HAO (HART-transparent Driver)

1066540000/01/12.11

67

Vibration

IEC 60068-2-6, test Fc, 1g, 2…100 Hz

Vibration, continuous

IEC 60068-2-64, test Fh, 1g, 3…100 Hz

Wire size, stranded wire

AWG 26…14 / 0.13…2.08 mm²

EMC immunity influence

0.5 % of span

Extended EMC immunity:
NAMUR NE 21, A criterion, burst

1 % of span

HART Communication

Frequency range

0.5…2.5 kHz

Signal / noise ratio

min. 60 dB (0.5…10 kHz)

Response time (0…90 %, 100…10 %)

< 5 ms

Default Settings

Low/high limit

3.8 mA / 20.5 mA