Input signals, Output signals supply and module status – Weidmuller ACT20X User Manual

Page 32

Advertising
background image

Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)

32

1066540000/01/12.11

51

52

53

54

Input signals

44

43

42

41

14

13

12

11

24

23

22

21

+

Current

RTD

TC

Connection, wi

res

+

Current

RTD

TC

Connection, wi

res

Output signals

Supply and module status

Supply -

Supply +19.2...31.2 VDC

N.C.

Module status

Module status

mA

mA

4...20 mA

+

-

42

41

44

43

-

+

-

-

mA

mA

4...20 mA

Analogue, 0/4...20 mA

2-wire supply +

2-wire supply -

2-wire supply +

2-wire supply -

Zone 0, 1, 2, 20, 21, 22 /
Cl. I/II/III, div. 1 gr. A-G

Zone 2 / FM Cl. 1,
div. 2, gr. A-D or safe area

Channel 1

Channel 1

Channel 2

Channel 2

Illustration 7-6: Applications

RTD Input

Pt100, according to

-200…+850 °C, IEC 60751

Ni100, according to

-60…+250 °C, DIN 43760

Sensor types
(* = without short circuit detection)

Pt10*, Pt20*, Pt50*, Pt100, Pt250, Pt300, Pt400,
Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000

Cable resistance per wire (max.)

50 Ω

Sensor current

nom. 0.2 mA

Effect of sensor cable resistance (3/4-wire)

< 0.002 Ω

Sensor error detection (programmable)

ON/OFF

Advertising