Weidmuller ACT20X User Manual

Page 35

Advertising
background image

Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)

1066540000/01/12.11

35

Status Relay

Safe Area

Zone 2 Installation

Voltage max.

125 V AC / 110 V

32 V AC / 32 V DC

Current max.

0.5 A AC / 0.3 A

0.5 A AC / 1 A DC

Power max.

62.5 VA / 32 W

16 VA / 32 W

Power Supply

Supply voltage

19.2…31.2 V DC

Max. consumption (2-channels)

≤ 3.5 W

Fuse

1.25 A / 250 V AC

Isolation Voltages (reinforced insulation), Test/Operation

Inputs / outputs / supply

2.6 kV AC / 300 V AC

Output 1 to output 2

1.5 kV AC / 150 V AC

Status relay to supply

1.5 kV AC / 150 V AC

Environmental Specifications

Ambient temperature

-20…+60 °C

Storage temperature

-20…+85 °C

Relative humidity (non-condensation)

< 95 %

Calibration temperature

+20…28 °C

General Specifications

Communications interface,
adapter / configuration software / FDT-DTM
device driver

CBX200 USB / "WI-Manager" / ACT20X DTM

Dimensions (H x W x D)

105.6 x 22.5 x 114.7 mm

Protection degree

IP20

Screw terminal torque

0.5 Nm

Vibration

IEC 60068-2-6, test Fc, 1g, 2…100 Hz

Vibration, continuous

IEC 60068-2-64, test Fh, 1g, 3…100 Hz

Wire size, stranded wire

AWG 26…14 / 0.13…2.08 mm²

EMC immunity influence

0.5 % of span

Extended EMC immunity:
NAMUR NE 21, A criterion, burst

1 % of span

Signal/Noise ratio

min. 60 dB (0…100 kHz)