Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)

1066540000/01/12.11

179

14

13

12

11

24

23

22

21

54
53
52
51

44
43
42
41

CH1

CH2

Configuration

CBX200 for

-20

Ta

+60ºC

in ha

zardous area

Not connected

in ha

zardous area

Not connected

mA

mA

+

-

+

-

ACT20X-(2)SAI-(2)HAO-S

Hazardous Classified Location

Class I / II / III, Division 1, Group A,B,C,D,E,F,G
Class I, Zone 0 / 1 / 2, Group IIC, IIB, IIA or
Zone 20 / 21

Unclassified Location or
Hazardous Classified Location

Class I, Division 2, Group A,B,C,D T4
Class I, Zone 2, Group IIC, IIB, IIA T4

Simple apparatus or
intrinsic safe apparatus
with entity parameters:

Vmax (Ui)

≥ Vt (Uo)

Imax (Ii)

≥ It (Io)

Pi

≥ Pt (Po)

Ca

≥ Ccable + Ci

La

≥ Lcable + Li

Illustration 7-56:

FM Installation Drawing

Terminal CH1 (11, 12), CH2 (21, 22)

Ex Output

U

o

28

V

I

o

93

mA

P

o

0.65

W

Group

C

o

L

o

IIC 0.08

F 4

mH

IIB 0.65

F 16

mH

IIA 2.15

F 32

mH