Weidmuller ACT20X User Manual

Page 34

Advertising
background image

Product Installation / Operation, ACT20X-HTI-SAO (Temperature/mA Converter)

34

1066540000/01/12.11

TC Input, Cold Junction Compensation (CJC)

CJC: external with ACT20X-CJC-HTI
(1160640000 or 1160650000)

+20…+28 °C ≤

1 °C

-20…+20 °C and +28…+60 °C≤

1.6 °C

CJC via internal sensor

t = internal temperature – ambient temperature

(2.0 °C + 0.2 °C * t)

Sensor error detection (programmable, only wire
breakage)

ON/OFF

Sensor error current:

when detecting
else


nom. 2 μA
0 μA

Current Input

Measurement range

0…20 mA

Programmable measurement ranges

0…20 / 4…20 mA

Input resistance

nom. 20 Ω + PTC 50 Ω

Sensor error detection (programmable)

ON/OFF

Current Output

Programmable signal ranges

0…20 mA / 4…20 mA / 20…0 mA / 20…4 mA

Load max.

4 mA / 600 Ω / 12 V DC

Load stability

0.01 % of span / 100 Ω

Sensor error detection

0 / 3.5 mA / 23 mA / none

Output limitation:

on 4…20 and 20…4 mA signals
on 0…20 and 20…0 mA signals


3.8…20.5 mA
0…20.5 mA

Current limit

≤ 28 mA

2-wire 4…20 mA Loop Powered Output

Signal range

4…20 mA

Load resistance

≤ (V

supply

– 3.5 V) / 0.023 A [Ω]

Load stability

≤ 0.01 % of span / 100 Ω

Max. external 2-wire supply

3.5…26 V DC

Effect of external 2-wire supply voltage variation

< 0.005 % of span / V