7.6.3 Electrical

Connections

Terminal

Function

Connector

Terminal

Function

Connector

11 Out

 41

In

12

Out +

42

In +

input

channel 1

13

43

In

14

Ex output

channel 1

44 In

+

input

channel 2

21 Out

 51

GND

22

Out +

52

+24 V DC

power supply

23

53 NC

24

Ex output

channel 2

54 COM

status relay

Table 7-12: Electrical Connections


7.6.4 Specifications

Features
 HART-compatible for 0.5...2.5 kHz
 Configuration and monitoring via FDT/DTM-Software "WI-Manager".
 The device can be mounted in the safe area and in Zone 2 / Division 2 and receive signals from Zone 0, 1,

2, 20, 21 and 22, as well as Class I/II/III, Division 1, Group A-G.

 The mA current signal inputs are completely electrically isolated.
 The device detects automatically whether an active or passive current signal is connected.
 Extended self diagnostic: Monitoring of error events (e.g. cable breakage) via status relay.
 Front LEDs indicates operation status and malfunction.
 3-way galvanic isolation between input, output and power supply.