Weidmuller ACT20X User Manual

Page 109

Advertising
background image

Appendix C. Installation Drawings ACT20X-SDI-HDO (Solenoid/Alarm Driver)

1066540000/01/12.11

109

Illustration 7-32:

FM Installation Drawing

Terminal CH1 (41, 42) and CH2 (43, 44)

Input

Voltage max

28 V DC

Trigger: NPN

Low < 2 V, High > 4 V

Trigger: PNP

Low < 8 V, High > 10 V

Terminal (11–12, 21–22)

Ex Output
8965400000 (ACT20X-SDI-HDO-L-S)
8965420000 (ACT20X-2SDI-2HDO-S)

Group

C

o

L

o

L

o

/R

o

U

o

28 V

IIC

80 nF

4.2 mH

54 µH/Ω

I

o

93 mA

IIB

640 nF

16.8 mH

218 µH/Ω

P

o

0.65 W

IIA

2.1 µF

32.6 mH

436 µH/Ω

Advertising