Weidmuller ACT20X User Manual

Page 128

Advertising
background image

Appendix D. Installation Drawings ACT20X-HUI-SAO (Universal Converter)

128

1066540000/01/12.11

Terminal (22–21, 21–22)

Input

Group

C

o

L

o

L

o

/R

o

U

o

16.6 V

IIC

0.4 µF

1000 mH

25 mH/Ω

I

o

0.2 mA

IIB

2.3 µF

1000 mH

100 mH/Ω

P

o

0.8 mW

IIA

9.5 µF

1000 mH

200 mH/Ω

Terminal (41, 42, 43, 44) and (51, 52, 53, 54)

Supply / Output

U

m

253 V, max. 400 Hz

Terminal (51, 52)

Supply

Voltage

19.2…31.2 V DC

Terminal (43, 44)

Relay Output

Non Hazardous
Location

Zone 2 Installation

Voltage max.

250 V AC / 30 V DC

32 V AC / 30 V DC

Current max.

2 A AC / 2 A DC

2 A AC / 2 A DC

Power max.

500 VA / 60 W

64 VA / 60 W

Terminal (53, 54)

Status Relay

Non Hazardous
Location

Zone 2 Installation

Voltage max.

125 V AC / 110 V DC

32 V AC / 32 V DC

Current max.

0.5 A AC / 0.3 A DC

0.5 A AC / 1 A DC

Power max.

62.5 VA / 32 W

16 VA / 32 W

Advertising