Weidmuller ACT20X User Manual

Page 76

Advertising
background image

Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)

76

1066540000/01/12.11

Terminal (51, 52)

Supply

Voltage

19.2…31.2 V DC

Power max.

3 W

Terminal (53, 54)

Status Relay

Non Hazardous
Location

Zone 2 Installation

Voltage max.

125 V AC / 110 V DC

32 V AC / 32 V DC

Current max.

0.5 A AC / 0.3 A DC

0.5 A AC / 1 A DC

Power max.

62.5 VA / 32 W

16 VA / 32 W

Terminal CH1 (41, 42) and CH2 (43, 44)

Digital Output, NPN Output

Voltage max.

30 V DC

Current max.

80 mA

Terminal CH1 (41, 42) and CH2 (43, 44)

Relay Output

Non Hazardous
Location

Zone 2 Installation

Voltage max.

250 V AC / 30 V DC

32 V AC / 30 V DC

Current max.

2 A AC / 2 A DC

2 A AC / 2 A DC

Power max.

500 VA / 60 W

64 VA / 60 W


Advertising