Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)

1066540000/01/12.11

69

Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)

ATEX Installation Drawing


The module is available in the following variants:

Order No.

Installation Drawing

Type

8965340000

4 50102 Sheet 1-2

ACT20X-HDI-SDO-RNO-S

8965350000

4 50102 Sheet 1-2

ACT20X-HDI-SDO-RNC-S

8965360000

4 50588 Sheet 1-2

ACT20X-HDI-SDO-S

8965370000

4 50589 Sheet 1-2

ACT20X-2HDI-2SDO-RNO-S

8965380000

4 50589 Sheet 1-2

ACT20X-2HDI-2SDO-RNC-S

8965390000

4 50590 Sheet 1-2

ACT20X-2HDI-2SDO-S

DANGER

For safe installation of ACT20X-(2)HDI-(2)SDO-(RNO/RNC)-S the following must be observed:
The module may only be installed by qualified personnel familiar with the national and
international laws, directives and standards that apply to this region.

DANGER

To prevent ignition of explosive atmospheres, disconnect power before servicing and do not

separate connectors when energized and an explosive gas mixture is present.


For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group IIB are applicable.
If the sensor circuits have been installed in a type of protection other than “intrinsic safety”, the module must
not be re-installed in type of protection ”intrinsic safety”.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The year of manufacture can be taken from the first two digits in the serial number.