Weidmuller ACT20X User Manual

Page 58

Advertising
background image

Product Installation / Operation, ACT20X-HAI-SAO (HART-transparent Repeater)

58

1066540000/01/12.11

Input signals

Output signals

Power Supply and Module Status

Zone 0, 1, 2, 20, 21, 22 /
Cl. I/II/III, div. 1 gr. A-G

Zone 2 / FM Cl. 1,
div. 2, gr. A-D or safe area

24

23

22

21

51

52

53

54

Module status

Module status

Gnd.

Supply +19.2...31.2 V DC

N.C.

14

12

11

13

42

41

44

43

mA

4...20 mA

mA

+

-

+

-

mA

mA

4...20 mA

+

-

Tx

2-wire supply +

2-wire supply –

2-wire supply +

2-wire supply –

Analogue, 4...20 mA

+

-

Current

Channel 1:

Channel 2:

-

-

+

-

Tx

+

-

Current

Illustration 7-17:

Applications

Current Input

Measurement range

3.5…23 mA

Alarm setpoint, low/high limit (programmable)

0…28 mA

Sensor error detection

< 1 mA

Current Output

Signal range (programmable)

3.5…23 mA

Load max.

20 mA / 600 Ω / 12 V DC

Load stability

≤ 0.01 % of span /100 Ω

Sensor error detection (programmable)

3.5 mA / 23 mA / none