3 electrical connections, 4 specifications, Features – Weidmuller ACT20X User Manual

Page 39: Electrical connections, Specifications

Advertising
background image

Product Installation / Operation, ACT20X-SDI-HDO (Solenoid/Alarm Driver)

1066540000/01/12.11

39

7.3.3 Electrical

Connections

Terminal

Function

Connector

Terminal

Function

Connector

11 GND

41 In

12

Ex 1

42

In +

input

channel 1

13 Ex

2

43 In

14 Ex

3

Ex output

channel 1

44 In

+

input

channel 2

21 GND

51 GND

22

Ex 1

52

+24 V DC

power supply

23

Ex 2

53

COM

24 Ex

3

Ex output

channel 2

54 NC

status relay

Table 7-6: Electrical Connections


7.3.4 Specifications

Features
 Solenoid/alarm driver for the control of solenoids, acoustic alarms and LEDs installed in the hazardous

area.

 Two hardware versions make it possible to choose either low (35 mA) or high (60 mA) current output with

1-channel or 2-channel versions.

 Configuration and monitoring via FDT/DTM-Software "WI-Manager".
 Selection of direct or inverted function for each channel and the possibility of reducing the output current to

the hazardous area to suit the application.

 The device can be mounted in the safe area and in Zone 2 / Division 2 and receive signals from Zone 0, 1,

2, 20, 21 and 22, as well as Class I/II/III, Division 1, Group A-G.

 Extended self diagnostic: Monitoring of error events via the individual status relay.
 LED indication: green and 2 yellow/red front LEDs to indicate operation status and malfunction.
 3-way galvanic isolation between input, output and supply, 2.6 kV AC.

Advertising