Atex installation drawing – Weidmuller ACT20X User Manual

Page 169

Advertising
background image

Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)

1066540000/01/12.11

169

Appendix F. Installation Drawings ACT20X-SAI-HAO (HART-transparent Driver)

ATEX Installation Drawing


The module is available in the following variants:

Order No.

Installation Drawing

Type

8965450000

4 53448 Sheet 1-2

ACT20X-SAI-HAO-S

8965460000

4 53448 Sheet 1-2

ACT20X-2SAI-2HAO-S

DANGER

For safe installation of ACT20X-(2)SAI-(2)HAO-S the following must be observed: The module
may only be installed by qualified personnel familiar with the national and international laws,
directives and standards that apply to this region.

DANGER

To prevent ignition of explosive atmospheres, disconnect power before servicing and do not

separate connectors when energized and an explosive gas mixture is present.


For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection of at
least IP54 according to type of protection Ex-n or Ex-e.
In type of protection “Ex ia Da” the parameters for intrinsic safety for gas group IIB are applicable.
The module must be installed in pollution degree 2, overvoltage category II as defined in EN 60664-1.
The year of manufacture can be taken from the first two digits in the serial number.

CBX200 – "WI-Manager" Software

For installation in Zone 2 / Division 2 the following must be observed:

- The CBX200 is an interface cable for configuration via PC.
- Configuration must be performed only in a safe area.

ATEX Certificate

DEKRA 11ATEX 0164 X

Marking

II 3 G Ex nA nC IIC T4 Gc
II (1) G [Ex ia Ga] IIC / IIB / IIA
II (1) D [Ex ia Da] IIIC

Standards

EN 60079-0: 2009, EN 60079-11: 2007, EN 60079-15: 2005
EN 60079-26: 2007, EN 61241-11: 2006