Weidmuller ACT20X User Manual

Page 163

Advertising
background image

Appendix E. Installation Drawings ACT20X-HAI-SAO (HART-transparent Repeater)

1066540000/01/12.11

163

Hazardous Classified Location

Class I / II / III, Division 1, Group A,B,C,D,E,F,G
Class I Zone 0 / 1 / 2 Group IIC, IIB, IIA, or
Zone 20 / 21

Unclassified Location or
Hazardous Classified Location
Class I, Division 2, Group A,B,C,D T4
Class I Zone 2, Group IIC, IIB, IIA T4

Simple Apparatus or
Intrinsic safe apparatus
with entity parameters:

Vmax (Ui) ≥ Vt (Uo)
Imax (li) ≥ It (Io)
Pi ≥ Pt (Po)
Ca ≥ C

cable

+ Ci

La ≥ L

cable

+Li

14

13

12

11

24

23

22

21

54
53
52
51

44
43
42
41

ACT20X-(2)HAI-(2)SAO-S

CH1

CH2

Configuration

CBX200 for

-20

Ta

+60ºC

in ha

zardous area

No

t connected

in ha

zardous area

No

t connected

Illustration 7-51:

FM Installation Drawing (2)

Terminal CH1 (11, 12), CH2 (21, 22)

Ex Input (External Current Source)

U

o

, V

OC

0

V

I

o

, I

SC

0

mA

P

o

0

mW

U

i

, V

max

30

V

I

i

, I

max

120

mA

P

i

0.85

W

C

i

2

nF

L

i

0

H