1066540000/01/12.11

Calibration temperature

+20…28 °C

General Specifications

Communications interface,
adapter / configuration software / FDT-DTM
device driver

CBX200 USB / "WI-Manager" / ACT20X DTM

Dimensions (H x W x D)

105.6 x 22.5 x 114.7 mm

Protection degree

IP20

Screw terminal torque

0.5 Nm

Vibration

IEC 60068-2-6, test Fc, 1g, 2…100 Hz

Vibration, continuous

IEC 60068-2-64, test Fh, 1g, 3…100 Hz

Wire size, stranded wire

AWG 26…14 / 0.13…2.08 mm²

EMC immunity influence

0.5 % of span

Extended EMC immunity:
NAMUR NE 21, A criterion, burst

1 % of span

Signal/Noise ratio

min. 60 dB (0…100 kHz)

Response time (0…90 %, 100…10 %):

Temperature input, programmable
mA / V input, programmable


1…60 s
0.4…60 s

Default Settings

Input type

Temperature

Connection type

3-wire

Temperature unit

°C

Temperature sensor type

Pt100

Temperature range

0…150 °C

Output current range

0…20 mA

Output current on error

23 mA

Analog output response time (1/10 s)

1 s

Relay Software Parameters / Default Settings

Function SETPOINT

Contact function

Normally Open (NO)

Setpoint

50 °C (input type temperature) / 50 %

Activation direction

Increasing

Hysteresis

1 °C (input type temperature) / 1 %