Weidmuller ACT20X User Manual
Page 27
Advertising
Product Installation / Operation, ACT20X-HDI-SDO (NAMUR Pulse Isolator)
1066540000/01/12.11
27
General Specifications
Communications interface,
adapter / configuration software / FDT-DTM
device driver
CBX200 USB / "WI-Manager" / ACT20X DTM
Dimensions (H x W x D)
105.6 x 22.5 x 114.7 mm
Protection degree
IP20
Screw terminal torque
0.5 Nm
Vibration
IEC 60068-2-6, test Fc, 1g, 2…100 Hz
Vibration, continuous
IEC 60068-2-64, test Fh, 1g, 3…100 Hz
Wire size, stranded wire
AWG 26…14 / 0.13…2.08 mm²
Response time for cable fault
< 200 ms
Default Settings
Channel 1 function
direct
Channel 2 function
direct
Short circuit indication
yes
Breakage indication
yes
Advertising