background image

Product Installation / Operation, ACT20X-HUI-SAO (Universal Converter)

48

1066540000/01/12.11

51

52

53

54

Input signals

Output signals

Power connection

Gnd.

Supply +19.2...31.2 VDC

NC

Device status

Supply via
power rail

Device status

Zone 0, 1, 2, 20, 21, 22 /
Cl. I/II/III, div. 1 gr. A-G

Zone 2 / FM Cl. 1,
div. 2, gr. A-D or

safe area

+

+

14

13

12

11

24

23

22

21

+

-

Tx

Cur rent

Voltage

Potenti-

ometer

RTD and lin. R

TC

* Order separately:
CJC connector

Connection, wir es

+

-

42

41

44

43

14

13

12

11

+

Analogue, 0/4...20 mA and relay

mA

mA

Relay

Relay

NO

Ch

a

n

n

e

l 1

:

Ch

a

n

n

e

l 2

:

*

Illustration 7-12:

Applications

RTD, Resistance and Potentiometer Input

Pt100, according to

-200…+850 °C, IEC 60751

Ni100, according to

-60…+250 °C, DIN 43760

Resistance
(without short circuit detection in the range
R = 0…18Ω, appr.)

0…10 kΩ

Potentiometer 10

Ω…10 kΩ

Sensor types
(* = without short circuit detection)

Pt10*, Pt20*, Pt50*, Pt100, Pt250, Pt300, Pt400,
Pt500, Pt1000, Ni50, Ni100, Ni120, Ni1000

Cable resistance per wire (max.)

50 Ω

Sensor current

nom. 0.2 mA

Effect of sensor cable resistance (3/4-wire)

< 0.002 Ω