Appendix A. Installation Drawings ACT20X-HDI-SDO (NAMUR Pulse Isolator)

1066540000/01/12.11

79

-20 = Ta = 60 °C

Class I, Division 2, Group A,B,C, D T4
or Class I, Zone 2 Group IIC T4

Non Hazardous area or

Simple Apparatus or

Intrinsically safe apparatus

with entity parameters:
Vmax (Ui) = Vt (Uo)

Imax (Ii) = It (Io)
Pi = Pt (Po)

Ca(Co) = Ccable + Ci
La(Co) = Lcable + Li

Class I/II/III, Division 1, Group A,B,C,D,E,F,G
or Class I, Zone 0/1 Group IIC, [AEx ia] IIC
or Class I, Zone 0/1 Group IIC, [Ex ia] IIC

NAMUR Sensor

Contact Sensor

Switch w Shunt

Switch

Hazardous area

Configuration in

safe area only!

CBX2

00 for

Configuration

ACT20X

11

12

13

-

+

-

CH2

CH1

+

14

21

22

23

24

41

42

43

44

51

52

53

54

Do not connected

in hazardous area!

Illustration 7-23:

FM Installation Drawing

Terminal CH1 (11, 12, 13, 14), CH2 (21, 22, 23, 24)

Ex Input

U

o

, V

t

10.6 V DC

I

o

, I

sc

12 mA DC

P

o

, P

t

32

mW

L

o

/R

o

, L

a

/R

a

1150

H/

Group

C

o

, C

a

L

o

, L

a

IIC or A, B

2

F 260

mH

IIB or C, E, F

6

F 780

mH

IIA or D, G

18

F 1000

mH