Installation, 1 general, 1 environment – Weidmuller ACT20X User Manual

Page 15: 2 unpacking, General, Environment, Unpacking

Advertising
background image

Installation

1066540000/01/12.11

15

5.

Installation

DANGER

Risk of explosion!
 For installation in Zone 2, install the

module in an outer enclosure with IP
protection of at least IP54.

 Protection must be according to type

of protection Ex-n or Ex-e.

WARNING

High voltage!
 Before removing or mounting the unit,

turn off power supply.

NOTICE

Material damage through ESD!
 Only carry out the following procedures under

ESD-safe conditions.

5.1 General

This product should only be installed by technically
qualified personnel with sufficient training in
instrumentation and control engineering.
VDE 0105 Part 1 / DIN EN 50110-1 defines qualified
personnel as electrically skilled workers,
electronically instructed personnel or personnel
meeting similar local standards.

5.1.1

Environment

This product is designed for use either indoors
(IP20) in a control panel, or in a weather-proof field
enclosure.
 Avoid direct sunlight, dust, high temperatures,

mechanical vibrations and shock as well as rain
and heavy moisture.

 If necessary, heating in excess of the stated limits

for ambient temperatures should be avoided by
ventilation.

 Product must be installed in pollution degree 2,

overvoltage category II as defined in EN 60664-1.

 Product is designed to be safe at least under an

altitude of up to 2000 m.

5.2 Unpacking

1

Check on receipt that the product received
corresponds to the one ordered.

2

Also make sure that installation instructions have
been supplied.

3

Unpack the product carefully.


 The use of stranded wires is not permitted for

mains wiring except for wires fitted with cable
ends.

 Descriptions of input/output and supply

connections are shown in the block diagram and
on the side label.

 The module is provided with field wiring terminals

and must be supplied from a power supply having
double/reinforced insulation.

 A power switch must be easily accessible and

close to the module.

 The power switch must be marked with a label

telling that it will switch off the voltage to the
module.

 Year of manufacture can be taken from the first

two digits in the serial number.

 Should there be any doubt as to the correct

handling of the module, contact your local
distributor.